Description
LaserDust Medium i Long Path (MP-LP)
NEO Monitors LaserDust™ Medium Path (MP), Long Path (LP), and Extra Long Path (XLP) Monitors are compact, optical dust monitors for true continuous in-situ measurement of dust concentration or opacity. The monitors are designed for measurement across pipes, stacks, and ducts with typical path lengths of 0.5 – 10 m LaserDustTM Monitors use a transmitter/receiver configuration to measure the dust concentration along the optical line of sight. Our true non-contact approach is superior to point type dust meters.
Technical data
Technical data
Specifications
Process temperature: Above dew point up to 700 ºC
Process pressure: 0.1 – 1.5 bar abs (optional windows for up to 5 bar)
Detection limit: < 0.5 mg/Nm3 (in scattered mode)
Measurement range: min. 0 – 15 mg/Nm3 (scattered mode), particle size >1micron max. 0 – 10.000 mg/Nm3 (transmissionmode), particle size >1micron
Resolution: 0.05 mg/Nm3
Optical path length**:
MP: 0.5 – 3 m
LP: 3 – 6 m
XLP: 6 – 10 m
Response time: 1 – 2 sec
Pulse mode: 50 ms
Environmental conditions
Operating temperature: -20 ºC to +55 ºC
Storage temperature: -20 ºC to +55 ºC
Protection classification: IP66
Inputs / Outputs
Analog output: 4 – 20 mA current loop (concentration, transmission)
Digital output: TCP/IP, MODBUS, Optional fibre optic
Relay output: High dust-, Warning – and Fault relays (normally closed-circuit relays)
Analog input: 4 – 20 mA process temperature and pressure reading